Electric Reliability Council of Texas (ERCOT)

Operations Messages

This section contains important messages from the ERCOT Control Room. Refresh this screen to see current operation messages. (Subscribe to Operations Messages Subscribe using any RSS ReaderRSS feed.)

May 2012 Apr 2012 Mar 2012 Feb 2012 Jan 2012 Dec 2011

Date Message Type Status
Dec 31 2011 20:23:43 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 31 2011 11:41:51 CST The BNBSW SPS #41 has been forced out of service. Operational Information Active
Dec 31 2011 06:50:14 CST On 12/30/11, a sudden loss of generation occurred at 15:57 totaling 629 MW, Frequency declined to 59.794, ERCOT load was 29, 700 MW. Operational Information Active
Dec 31 2011 05:31:20 CST DAM OD 01/01/2012 will be using West to North (W_TO_N) generic constraint limit of 2127 MW for hours 1-17, 24 and 1557 MW for hours 18-23. OCN Active
Dec 31 2011 05:23:28 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 31 2011 01:20:55 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 30 2011 07:32:45 CST No sudden loss of generation greater than 450 MW occurred on 12/29/11. Operational Information Active
Dec 30 2011 07:29:29 CST ERCOT has cancelled the following notice: The Barney Davis SPS has returned to service. Operational Information Cancelled
Dec 30 2011 07:27:33 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 30 2011 05:01:32 CST DAM OD 12/31/2011 will be using West to North (W_TO_N) generic constraint limit of 2127 MW for hours 1-9, 11-18, 21-24 and 1557 MW for hours 10, 19-20 OCN Active
Dec 30 2011 03:53:00 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 29 2011 23:37:59 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 29 2011 19:02:08 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 29 2011 14:33:27 CST ERCOT has cancelled the following notice: ERCOT taking manual action for Stryker Creek 345kv CB 3255 outage. Operational Information Cancelled
Dec 29 2011 14:18:42 CST ERCOT taking manual action for Stryker Creek 345kv CB 3255 outage. Operational Information Active
Dec 29 2011 06:52:22 CST On 12/28/11, a sudden loss of generation occurred at 09:49 totaling 719 MW. Frequency declined to 59.796 HZ, ERCOT load was 37, 472 MW. Operational Information Active
Dec 29 2011 05:47:12 CST DAM OD 12/30/2011 will be using West to North (W_TO_N) generic constraint limit of 2127 MW for hours 1-5, 14-17, 23, 24 and 1557 MW for hours 6-13, 18-22. OCN Active
Dec 28 2011 11:57:49 CST ERCOT has cancelled the following notice: The Austrop #1 SPS has been taken out of service. Operational Information Cancelled
Dec 28 2011 08:21:36 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 28 2011 08:17:15 CST No sudden loss of generation greater than 450 MW occurred on 12/27/11. Operational Information Active
Dec 28 2011 07:48:36 CST The Austrop #1 SPS has been taken out of service. Operational Information Active
Dec 28 2011 05:49:52 CST DAM OD 12/29/2011 will be using West to North (W_TO_N) generic constraint limit of 2121 MW for hours 1-4, 16, 24 and 1552 MW for hours 5-15, 17-23. OCN Active
Dec 27 2011 22:29:59 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 27 2011 07:26:19 CST On 12/26/11, a sudden loss of generation occurred at 03:46 totaling 546 MW. Frequency declined to 59.834 HZ, ERCOT load was 29, 654 MW. Operational Information Active
Dec 27 2011 05:33:22 CST DAM OD 12/28/2011 will be using West to North (W_TO_N) generic constraint limit of 1558 MW for hours 1, 5-24 and 2129 MW for hours 2-4. OCN Active
Dec 26 2011 06:28:49 CST No sudden loss of generation greater than 450 MW occurred on 12/25/11. Operational Information Active
Dec 26 2011 05:29:09 CST DAM OD 12/27/2011 will be using West to North (W_TO_N) generic constraint limit of 1558 MW for hours 1, 2, 4-24 and 2129 MW for hour 3. OCN Active
Dec 25 2011 16:16:29 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 25 2011 09:11:50 CST Physical Responsive Capability < 3000 MW: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Active
Dec 25 2011 08:15:11 CST No sudden loss of generation greater than 450 MW occurred on 12/24/11. Operational Information Active
Dec 25 2011 05:29:12 CST DAM OD 12/26/2011 will be using West to North (W_TO_N) generic constraint limit of 1558 MW for hours 1-13, 18-24 and 2129 MW for hours 14-17. OCN Active
Dec 24 2011 21:08:15 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 24 2011 18:06:27 CST Physical Responsive Capability < 3000 MW: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Active
Dec 24 2011 12:03:04 CST The Barney Davis SPS has returned to service. Operational Information Active
Dec 24 2011 06:55:28 CST No sudden loss of generation greater than 450 MW occurred on 12/23/11. Operational Information Active
Dec 24 2011 05:30:25 CST DAM OD 12/25/2011 will be using West to North (W_TO_N) generic constraint limit of 1558 MW for all hours (HE 1-24). OCN Active
Dec 23 2011 23:44:16 CST ERCOT has cancelled the following notice: AEN Austrop Autotransformer SPS has been placed back in service. Operational Information Cancelled
Dec 23 2011 05:36:56 CST On 12/22/11, a sudden loss of generation occurred at 05:13 totaling 760 MW. Frequency declined to 59.799 HZ, ERCOT load was 30, 709 MW. Operational Information Active
Dec 23 2011 05:22:58 CST DAM OD 12/24/2011 will be using West to North (W_TO_N) generic constraint limit of 1558 MW for all hours (HE 1-24). OCN Active
Dec 22 2011 11:14:41 CST AEN Austrop Autotransformer SPS has been placed back in service. Operational Information Active
Dec 22 2011 10:13:43 CST Eagle Pass DC Tie (South DC Tie) will be unavailable until 03/11/2012 Operational Information Active
Dec 22 2011 10:03:22 CST ERCOT has cancelled the following notice: The LCRA Austrop SPS on 345 kv line T-229 has been put back into service. Operational Information Cancelled
Dec 22 2011 07:42:46 CST No sudden loss of generation greater than 450 MW occurred on 12/21/11. Operational Information Active
Dec 22 2011 05:21:43 CST DAM OD 12/23/2011 will be using West to North (W_TO_N) generic constraint limit of 2129 MW for hours 1-5 and 1558 MW for hours 6-24. OCN Active
Dec 21 2011 09:23:36 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 21 2011 08:00:22 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 21 2011 07:15:15 CST No sudden loss of generation greater than 450 MW occurred on 12/20/11. Operational Information Active
Dec 21 2011 05:23:27 CST DAM OD 12/22/2011 will be using West to North (W_TO_N) generic constraint limit of 2126 MW for hours 1-5, 24 and 1556 MW for hours 6-23. OCN Active
Dec 20 2011 19:19:22 CST ERCOT has cancelled the following notice: The Railroad DC Tie will be available for Import only thru Friday, December 16, 2011 at 1700 due to a Planned Outage. Operational Information Cancelled
Dec 20 2011 15:13:27 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 20 2011 07:03:28 CST No sudden loss of generation greater than 450 MW occurred on 12/19/11. Operational Information Active
Dec 20 2011 05:12:32 CST DAM OD 12/21/2011 will be using West to North (W_TO_N) generic constraint limit of 1556 MW for all hours 1-24. OCN Active
Dec 19 2011 20:26:18 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 19 2011 17:47:19 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 19 2011 09:25:18 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 19 2011 08:45:37 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 19 2011 07:53:27 CST On 12/18/11, a sudden loss of generation occurred at 08:15 totaling 780 MW. Frequency declined to 59.766 HZ, ERCOT load was 31, 000 MW. Operational Information Active
Dec 19 2011 07:10:45 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 19 2011 05:41:43 CST ERCOT has cancelled the following notice: The LCRA Austrop SPS on 345 kv line T-229 has been taken out of service. Operational Information Cancelled
Dec 19 2011 05:20:36 CST DAM OD 12/20/2011 will be using West to North (W_TO_N) generic constraint limit of 1027 MW for all hours 1-24. OCN Active
Dec 19 2011 03:17:36 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 18 2011 20:54:59 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 18 2011 06:55:40 CST No sudden loss of generation greater than 450 MW occurred on 12/17/11. Operational Information Active
Dec 18 2011 05:02:12 CST DAM OD 12/19/2011 will be using West to North (W_TO_N) generic constraint limit of 1027 MW for all hours 1-24. OCN Active
Dec 17 2011 06:45:34 CST No sudden loss of generation greater than 450 MW occurred on 12/16/11. Operational Information Active
Dec 17 2011 05:47:44 CST DAM OD 12/18/2011 will be using West to North (W_TO_N) generic constraint limit of 1027 MW for all hours 1-24. OCN Active
Dec 16 2011 15:36:57 CST ERCOT has cancelled the following notice: North DC Tie will be in Outage Friday 12/16/11 at 05:00 until 17:00 (OKLA) 345kV disconnected 5598_S will open the Oklaunion (OKLA) to North HVDC (DCTM) 345kV circuit DCT_OKL Operational Information Cancelled
Dec 16 2011 11:06:34 CST The LCRA Austrop SPS on 345 kv line T-229 has been put back into service. Operational Information Active
Dec 16 2011 10:16:46 CST DC Tie Outage: The DC_S (Eagle Pass) DC Tie will be unavailable from 12/16/2011 through 03/10/2012 due to a planned outage. Operational Information Active
Dec 16 2011 06:53:11 CST On 12/15/11, a sudden loss of generation occurred at 13:16 totaling 607 MW. Frequency declined to 59.791 HZ, ERCOT load was 34, 541 MW. Operational Information Active
Dec 16 2011 04:51:41 CST DAM OD 12/17/2011 will be using West to North (W_TO_N) generic constraint limit of 1027 MW for all hours 1-24. Operational Information Active
Dec 15 2011 07:04:36 CST On 12/14/11, a sudden loss of generation occurred at 14:58 totaling 560 MW. Frequency declined to 59.827 HZ, ERCOT load was 33, 657 MW. Operational Information Active
Dec 15 2011 05:46:05 CST DAM OD 12/16/2011 will be using West to North (W_TO_N) generic constraint limit of 2280 MW for hours 1-5, 1916 MW for hours 6-8, 20-24 and 1901 MW for 9-19. OCN Active
Dec 14 2011 23:43:59 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 14 2011 19:45:32 CST North DC Tie will be in Outage Friday 12/16/11 at 05:00 until 17:00 (OKLA) 345kV disconnected 5598_S will open the Oklaunion (OKLA) to North HVDC (DCTM) 345kV circuit DCT_OKL Operational Information Active
Dec 14 2011 17:39:38 CST Physical Responsive Capability < 3000 MW: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Active
Dec 14 2011 09:53:00 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 14 2011 06:22:28 CST No sudden loss of generation greater than 450 MW occurred on 12/13/11. Operational Information Active
Dec 14 2011 05:36:32 CST DAM OD 12/15/2011 will be using Valley Import(VALIMP) generic constraint limit of 400 MW for all hours (HE 1-24). OCN Active
Dec 14 2011 05:24:23 CST DAM OD 12/15/2011 will be using West to North (W_TO_N) generic constraint limit of 2280 MW for hours 1-6, 24 and 1917 MW for hours 7-23. OCN Active
Dec 13 2011 11:52:20 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Active
Dec 13 2011 07:18:08 CST No sudden loss of generation greater than 450 MW occurred on 12/12/11. Operational Information Active
Dec 13 2011 05:01:51 CST DAM OD 12/14/2011 will be using West to North (W_TO_N) generic constraint limit of 2282 MW for hours 1-6, 24 and 1918 MW for hours 7-23. OCN Active
Dec 12 2011 11:48:59 CST The Railroad DC Tie will be available for Import only thru Friday, December 16, 2011 at 1700 due to a Planned Outage. Operational Information Active
Dec 12 2011 10:05:15 CST The LCRA Austrop SPS on 345 kv line T-229 has been taken out of service. Operational Information Active
Dec 12 2011 08:57:33 CST The Railroad DC Tie will be unavailable for Export thru Friday, December 16, 2011 at 1700 due to an Outage. Operational Information Active
Dec 12 2011 08:51:47 CST The AEN Austrop Autotransformer SPS has been taken out of service. Operational Information Active
Dec 12 2011 07:48:04 CST No sudden loss of generation greater than 450 MW occurred on 12/11/11. Operational Information Active
Dec 12 2011 06:02:39 CST The Railroad DC Tie will be unavailable for Export thru Friday, December 15, 2011 at 1700 due to an Outage. Operational Information Active
Dec 12 2011 05:15:59 CST DAM OD 12/13/2011 will be using West to North (W_TO_N) generic constraint limit of 2287 MW for hours 1-5, 11-15, 24 and 1922 MW for hours 6-10, 16-23. OCN Active
Dec 11 2011 14:55:38 CST AS Responsibility Check for OD 12122011 was inadvertently triggered at 1446. Please disregard any messages for AS Responsibility at this time. The event will be re-run at 1544. OCN Active
Dec 11 2011 12:41:34 CST ERCOT has delayed the deadline for the posting of the DAM solutions for OD Dec 12, 2011 due to long solution time. ERCOT will post notification when DAM is complete. Advisory Active
Dec 11 2011 05:52:55 CST No sudden loss of generation greater than 450 MW occurred on 12/10/11. Operational Information Active
Dec 11 2011 05:22:45 CST DAM OD 12/12/2011 will be using West to North (W_TO_N) generic constraint limit of 2287 MW for hours 1-3, 24 and 1922 MW for hours 4-23. OCN Active
Dec 10 2011 20:14:16 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 10 2011 20:14:12 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 10 2011 17:49:46 CST Physical Responsive Capability < 3000 MW: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 10 2011 07:31:22 CST No sudden loss of generation greater than 450 MW occurred on 12/08/11. Operational Information Active
Dec 10 2011 07:28:09 CST No sudden loss of generation greater than 450 MW occurred on 12/09/11. Operational Information Active
Dec 10 2011 05:26:35 CST DAM OD 12/11/2011 will be using West to North (W_TO_N) generic constraint limit of 1922 MW for hours 1-14, 17-24 and 2287 MW for hours 15, 16. OCN Active
Dec 09 2011 12:21:37 CST ERCOT has cancelled the following notice: ERCOT is taking manual action for RYSSW bus outage. Operational Information Cancelled
Dec 09 2011 06:20:14 CST ERCOT is taking manual action for RYSSW bus outage. Operational Information Cancelled
Dec 09 2011 05:25:06 CST DAM OD 12/10/2011 will be using West to North (W_TO_N) generic constraint limit of 1918 MW for hours 1-13, 18-24 and 2281 MW for hours 14-17. OCN Active
Dec 09 2011 03:52:36 CST ERCOT has cancelled the following notice: ERCOT is working from the Primary Control Center. Operational Information Cancelled
Dec 08 2011 19:20:27 CST ERCOT has cancelled the following notice: The Eagle Pass DC Tie is unavailable until further notice due to a Forced Outage. Operational Information Cancelled
Dec 08 2011 09:09:19 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 08 2011 07:58:46 CST The North HVDC DC Tie will be unavailable from 12/16/2011 05:00 through 12/16/2011 17:00 due to a planned outage. Operational Information Active
Dec 08 2011 07:09:51 CST On 12/07/11, a sudden loss of generation occurred at 20:31 totaling 473 MW. Frequency declined to 59.903 HZ, ERCOT load was 44, 269 MW. Operational Information Active
Dec 08 2011 05:23:16 CST DAM OD 12/9/2011 will be using West to North (W_TO_N) generic constraint limit of 1925 MW for all hours. OCN Active
Dec 07 2011 23:50:26 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 07 2011 14:36:51 CST ERCOT has cancelled the following notice: ERCOT is taking manual actions due to a stability limit. This limit is caused by a planned outage on the MNSES to Farmersville #1 345 KV line. Operational Information Cancelled
Dec 07 2011 12:07:14 CST ERCOT has cancelled the following notice: The AEN AUSTRO Transformers SPS and the LCRA AUSTRO AT2 SPS has been taken out of service. Operational Information Cancelled
Dec 07 2011 09:09:00 CST The AEN AUSTRO Transformers SPS and the LCRA AUSTRO AT2 SPS has been taken out of service. Operational Information Cancelled
Dec 07 2011 07:03:37 CST No sudden loss of generation greater than 450 MW occurred on 12/06/11. Operational Information Active
Dec 07 2011 06:06:51 CST ERCOT is taking manual actions due to a stability limit. This limit is caused by a planned outage on the MNSES to Farmersville #1 345 KV line. Operational Information Cancelled
Dec 07 2011 05:44:30 CST DAM OD 12/8/2011 will be using West to North (W_TO_N) generic constraint limit of 1619 MW for hours 1-20 and 1925 MW for hours 21-24. OCN Active
Dec 06 2011 18:36:56 CST ERCOT has cancelled the following notice: ERCOT is working from alternate control center. Operational Information Cancelled
Dec 06 2011 18:10:29 CST ERCOT has cancelled the following notice: ERCOT is working from alternate control center. Operational Information Cancelled
Dec 06 2011 17:06:12 CST ERCOT is working from the Primary Control Center. Operational Information Cancelled
Dec 06 2011 07:18:07 CST No sudden loss of generation greater than 450 MW occurred on 12/05/11. Operational Information Active
Dec 06 2011 05:31:54 CST DAM OD 12/7/2011 will be using West to North (W_TO_N) generic constraint limit of 1625 MW for all hours. OCN Active
Dec 06 2011 05:22:39 CST ERCOT is working from alternate control center. Operational Information Cancelled
Dec 05 2011 18:17:18 CST No sudden loss of generation greater than 450 MW occurred on 12/04/11. Operational Information Active
Dec 05 2011 14:59:06 CST ERCOT has completed a price analysis on DAM OD 12-06-2011 and identified a need for price correction. Operating intervals involved are operating hour 1 to 24. Totally 1 Settlement Point (DC_S) was involved. Complete price correction data will be posted on Market Information System as soon as possible but no later than 10:00 am on 12-07-2011. Advisory Active
Dec 05 2011 12:51:11 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 05 2011 12:36:51 CST ERCOT has cancelled the following notice: This is a test of the ERCOT notification service. Operational Information Cancelled
Dec 05 2011 12:34:55 CST ERCOT has cancelled the following notice: This is a test of the ERCOT notification service. Operational Information Cancelled
Dec 05 2011 12:32:38 CST ERCOT has cancelled the following notice: “ERCOT IS CONDUCTING A WINTER STORM DRILL. ALL OF THE FOLLOWING INSTRUCTIONS ARE FOR SIMULATION AND TEST PURPOSES ONLY. NO REAL-TIME ACTION IS TO BE TAKEN.” All communication testing for the Winter Storm Drill will begin at 07:30 Remember calls directed to ERCOT should be to the numbers provided on the Designated Drill Phone Numbers for Contracting ERCOT sheet. If you have any question, call 512-248-3802 Operational Information Cancelled
Dec 05 2011 05:59:07 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 05 2011 05:09:45 CST DAM OD 12/6/2011 will be using West to North (W_TO_N) generic constraint limit of 1944 MW for hours 1-6, and 1635 MW for hours 7-24. OCN Active
Dec 05 2011 01:20:04 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 04 2011 21:33:18 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 04 2011 06:41:10 CST No sudden loss of generation greater than 450 MW occurred on 12/03/11. Operational Information Active
Dec 04 2011 04:56:02 CST DAM OD 12/5/2011 will be using West to North (W_TO_N) generic constraint limit of 2312 MW for hours 1-6, and 1944 MW for hours 7-24. OCN Active
Dec 04 2011 02:40:33 CST ERCOT has cancelled the following notice: At 0909, ERCOT issued an OCN for Projected Reserve Capacity shortage for HE 1100 to HE 1300. OCN Cancelled
Dec 03 2011 14:05:09 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 03 2011 12:02:53 CST ERCOT has cancelled the following notice: This is a test of the ERCOT notification service. Operational Information Cancelled
Dec 03 2011 11:37:28 CST Test Message on Notice Builder/Twitter: This is a test of the ERCOT notification service. Operational Information Cancelled
Dec 03 2011 09:25:07 CST Physical Responsive Capability < 3000 MW: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 03 2011 09:15:47 CST At 0909, ERCOT issued an OCN for Projected Reserve Capacity shortage for HE 1100 to HE 1300. OCN Cancelled
Dec 03 2011 07:12:01 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 03 2011 06:54:23 CST No sudden loss of generation greater than 450 MW occurred on 12/02/11. Operational Information Active
Dec 03 2011 05:01:50 CST DAM OD 12/4/2011 will be using West to North (W_TO_N) generic constraint limit of 2312 MW for hours 1-10, 15-17, 23-24 and 1944 MW for hours 11-14, 18-22. OCN Active
Dec 03 2011 03:47:43 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 02 2011 21:38:55 CST ERCOT has cancelled the following notice: ERCOT is deploying Non-Spin Reserve for Dodegal5 constraint. Operational Information Cancelled
Dec 02 2011 20:37:57 CST ERCOT has cancelled the following notice: ERCOT is issuing an OCN for Projected Reserve Capacity shortage for HE18 thru HE20. OCN Cancelled
Dec 02 2011 20:35:53 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 02 2011 15:11:01 CST ERCOT is issuing an OCN for Projected Reserve Capacity shortage for HE18 thru HE20. OCN Cancelled
Dec 02 2011 14:12:39 CST ERCOT has cancelled the following notice: ERCOT is issuing a Watch due to Physical Responsive Capability being below 2500 MW. Watch Cancelled
Dec 02 2011 13:25:15 CST ERCOT has cancelled the following notice: ERCOT is issuing a Watch due to Physical Responsive Capability being below 2500 MW. Watch Cancelled
Dec 02 2011 13:05:05 CST ERCOT has cancelled the following notice: ERCOT is deploying 1/2 of Non Spin Reserve Operational Information Cancelled
Dec 02 2011 13:04:07 CST ERCOT is deploying Non-Spin Reserve for Dodegal5 constraint. Operational Information Cancelled
Dec 02 2011 10:05:40 CST ERCOT is deploying 1/2 of Non Spin Reserve Operational Information Cancelled
Dec 02 2011 09:44:15 CST Physical Responsive Capability < 2500 MW: ERCOT is issuing a Watch due to Physical Responsive Capability being below 2500 MW. Watch Cancelled
Dec 02 2011 09:44:15 CST Physical Responsive Capability < 2500 MW: ERCOT is issuing a Watch due to Physical Responsive Capability being below 2500 MW. Watch Cancelled
Dec 02 2011 09:15:38 CST Physical Responsive Capability < 3000 MW: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 02 2011 07:54:32 CST No sudden loss of generation greater than 450 MW occurred on 12/01/11. Operational Information Active
Dec 02 2011 05:01:53 CST DAM OD 12/3/2011 will be using West to North (W_TO_N) generic constraint limit of 2322 MW for hours 1-17, 23, 24 and 1952 MW for hours 18-22. OCN Active
Dec 02 2011 04:31:49 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 02 2011 01:41:19 CST The Eagle Pass DC Tie is unavailable until further notice due to a Forced Outage. Operational Information Cancelled
Dec 01 2011 18:23:13 CST West-North Stability Limit: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 01 2011 14:37:54 CST ERCOT has cancelled the following notice: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 01 2011 11:36:26 CST Physical Responsive Capability < 3000 MW: ERCOT is issuing an Advisory due to Physical Responsive Capability being below 3000 MW Advisory Cancelled
Dec 01 2011 08:44:26 CST ERCOT has cancelled the following notice: ERCOT is constraining for the West-North stability limit. Operational Information Cancelled
Dec 01 2011 07:12:04 CST No sudden loss of generation greater than 450 MW occurred on 11/30/11. Operational Information Active